Location: Home >>Product >>Fault Location

Distributed fault location device for transmission lines

型號:DX-WPS100-GZ01

Online Inquiry+8618926454155


Product details

Distributed fault location and hidden danger monitoring device for transmission lines

model:DX-WPS100-GZ01

1、 Demand analysis

With the increasing number of high-voltage long-distance overhead transmission lines, transmission lines, as the link of energy transmission, are the basis for the safe and stable operation of the whole system; Once a fault occurs on the transmission line, it is necessary to find the fault point as soon as possible, eliminate the fault and restore power supply. However, as high-voltage and ultra-high voltage transmission lines are often exposed to different environments and distributed in a wide geographical area, the operating environment is harsh; Therefore, it is also a place where many faults occur in the power system. It is very important to quickly and accurately find the fault point after the line fault, not only for timely repair of the line and rapid restoration of power supply, but also for the security, stability and economic operation of the entire power system.


2、 Working principle

The distributed fault location and hidden danger monitoring device for transmission lines adopts the distributed traveling wave measurement technology. The monitoring terminals are distributed on the transmission line conductors. The power frequency fault signals and traveling wave fault signals near the line fault time point are collected at high potential and sent back to the background data center in 4G/5G wireless ways. Through the comprehensive analysis of the data center, the fault point can be quickly and accurately determined according to different fault characteristics, Improve fault location accuracy to improve fault line patrol efficiency, and also capture transient fault traveling wave waveform to intelligently identify whether the fault is a lightning strike fault or a non lightning strike fault, and whether the lightning strike fault is a shielding strike or a counterattack. The diagnosis results are displayed in two ways: web and SMS, and sent to users, which is helpful to timely repair the fault line and ensure the safe and stable operation of the whole power grid.


3、 Product Functions

(1) Basic configuration of fault location monitoring: main control unit, fault location monitoring unit, communication unit, inductive power supply unit, solar power supply unit, mounting bracket and auxiliary materials.

(2) Detection and calculation of fault distance: it can accurately detect and record the distance of single-phase ground fault, interphase short circuit fault, open circuit fault and instantaneous fault of the line online;

(3) High precision fault location: it can accurately determine the fault section of transmission line, and the reliability of section location is more than 99%;

(4) The error is not more than 300 meters: it can accurately determine the fault location of the transmission line, and the location error is 300 meters

(5) Fault cause identification function: it can identify lightning strike fault and non lightning strike fault, and the accuracy of lightning strike and non lightning strike fault identification is more than 95%;

(6) High identification accuracy: it can identify shielding failure and counterattack failure, and the identification accuracy of lightning strike fault nature is more than 90%

(7) Dual RAM recording technology: dual RAM recording technology is adopted to eliminate the "dead zone of recording" of transient signals and prevent the omission of fault data caused by lightning current interference;

(8) It can record line lightning current, locate lightning strike points and count lightning strike times online;

(9) It can detect line load current online, including timing return and call to measure load current data;

(10) The software has the functions of automatic fault identification, output alarm and data file storage;

(11) 4G/5G wireless transmission: 4G/5G network encryption transmission, measurement;

(12) Support remote upgrade: support remote parameter setting and program upgrade


4、 Technical parameters

Serial No

category

project

technical parameter

1     

Overall performance

Complete machine configuration

Main control unit, fault location monitoring unit, communication unit, inductive power supply unit, solar power supply unit and installation auxiliary materials.

2     

Overall quality

Less than 15KG

3     

texture of material

Aluminum mold body

4     

Fault location monitoring unit

Fault location sensor

Interval positioning reliability ≥ 99%; Positioning error ≤ 100m

5     

Detect line length

30km

6     

Traveling wave sensor broadband

1kHz2MHz

7     

Traveling wave sampling rate

5MHz

8     

Single conductor fault current measurement range

10A15000A(Valid value)

9     

Continuous recording duration of traveling wave current

1000μs

10    

Communication unit

communication mode

All Netcom 4G/5G/WIFI wireless transmission

11    

Data security

VPN dedicated channel can be used for communication with the master station, and encryption transmission is optional.

12    

Access protocol

Access to monitoring platforms of provincial power companies such as Southern Power Grid and State Grid

13    

Power supply unit

Power supply mode

The normal working current range of induction power supply and solar power supply is 30~1000A;

14       

Power supply duration

The power supply requirement that the device can operate normally for 30 days without continuous illumination.

15       

Other parameters

work environment

Working temperature: - 40~+70 ℃; Relative humidity: 5-99% RH

16    

Overall service life

More than 8 years

17    

Degree of protection

IP67




Contact us

Shenzhen Dinsee Smart Technology Co.,Ltd
Tel:0755-21612345?Mobile&Whatsapp:+8618926454155
Fax:0755-21612345Whatsapp:+8618926454155E-Mail:business@szdx.com
Address: Building 2,xiangyuer Industry Part,NO.8 Longsheng Road,Longgang District,Shenzhen 518126,China

The online monitoring, distributed fault location and cable online monitoring equipment for power transmission and distribution lines launched by SHENZHEN DINSEE SMART TECHNOLOGY CO.,LTD. has been widely used in Southern Power Grid and State Grid, and has achieved good results.

Record No.: Yue ICP Bei 2022070794-1 | Website Map XML Map

主站蜘蛛池模板: 亚洲精品少妇30p| 寂寞骚妇被后入式爆草抓爆| 中日韩va无码中文字幕 | 欧美人与动欧交视频| 国产偷窥熟精品视频| 中文字幕人妻熟女人妻a片| 国产真人无码作爱免费视频| 国产偷国产偷亚洲高清人| 久久婷婷综合缴情亚洲狠狠| 久久精品中文字幕免费| 日本毛x片免费视频观看视频| 大肉大捧一进一出好爽mba| 99久久国产综合精品成人影院| 色偷偷av男人的天堂京东热| 在线亚洲午夜片av大片| 国产成本人片无码免费| 国产偷人激情视频在线观看| 久久国内精品自在自线400部| 在线 | 一区二区三区| 伊人色综合久久天天人守人婷| 亚洲色一色噜一噜噜噜| 欧美黑人巨大videos精品| 日韩精品成人av在线观看| 鲁丝久久久精品av论理电影网| 特级a欧美做爰片第一次| 性色av一区二区三区人妻| 激情综合五月| 麻花传媒mv在线观看| 国产手机在线精品| 玩弄少妇人妻| 亚洲欧美日韩成人一区二区三区| 日本乱码一区二区三区不卡| 国产精品成人3p一区二区三区| 中文字幕丰满伦子无码| 大肉大捧一进一出好爽视频mba| 日本久久高清一区二区三区毛片| 国产精品h片在线播放| 热99re久久精品天堂| 亚洲精品一区| 国产成人精品av| 波多野吉av无码av乱码在线|